Freestanding masonry wall

A garden wall or fence: a concrete masonry stem cantilevered from a continuous concrete footing, under wind or a seismic coefficient. The stem is designed at the top of the footing to TMS 402-22 (reinforced or unreinforced, strength or allowable stress, with the switch in the toolbar); the footing is checked for overturning, sliding and soil bearing. US and metric units.

Edition. TMS 402-22 is not on hand: the stem uses the shared masonry library (the 402-13 text with the 402-22 numbering where confirmed, as the other masonry types). The wind on a freestanding wall follows ASCE 7-22 29.3; whether 7-22 writes Kd inside Eq. 29.3-1 is to be confirmed. CMHA TEK 14-16B, Concrete Masonry Fence Design, is on hand and its tables are compared below.

Inputs of the freestanding wall

  • Wall: exposed height above grade; the stem below grade to the top of the footing (TEK 14-16B uses 18 in. for 4 and 6 ft fences, 24 in. for 8 ft; check frost depth); thickness; reinforced or unreinforced; grouting (fully, or only the cells with bars); f′m; for unreinforced stems the mortar; for reinforced stems the bar, its spacing and grade (bars at the centre of the wall); the wall weight with its grout.
  • Wind: a strength level pressure entered, or computed from the basic wind speed, exposure, Kzt, Ke, Kd (0.85 for solid freestanding walls) and the force coefficient Cf of ASCE 7-22 Figure 29.3-1, which you read for the wall's proportions: 1.3 for a long wall with clearance ratio s/h = 1 (case A), up to 1.8 for short walls, and higher near free ends (case C). Kz is taken at the top of the wall, at least 15 ft.
  • Seismic: a horizontal coefficient on the stem's weight at strength level, from ASCE 7-22 Chapter 15 for the structure; 0 for none.
  • Footing and soil: width, thickness and the stem's offset from its centre (both wind directions are checked); concrete and soil unit weights; the allowable bearing pressure (geotechnical report or IBC Table 1806.2); the friction coefficient; whether to count the lateral bearing pressure of IBC 1806.2 down to the footing bottom; the factors of safety for overturning and sliding. IBC 1807.2.3 asks 1.5 for retaining walls; for a fence it is your choice, 1.5 prefilled.

Auto-design (editor toolbar) varies the wall thickness, the bar and spacing and the footing width. Objective: the least masonry, steel and footing concrete. The wall weight is an input and is kept.

Checks performed

CheckBasis
Stem flexure, reinforcedStrength: 0.80 f′m stress block (face shell, or face shell and grouted cells), φ from the net tensile strain (TMS 402-22 9.3.2, Table 9.1.4). Allowable stress: cracked transformed section (8.3)
Stem flexure, unreinforcedNet tension M/S − P/A at most φ fr (Table 9.1.9.1, φ = 0.60) or the allowable tension of Table 8.2.4.2
Stem shear9.3.3.1.2 or 8.3.5 (reinforced, γg = 0.75 when partially grouted); 9.2.6 or 8.2.6 on the webs (unreinforced)
OverturningUnfactored dead load (stem, footing, soil on the footing) about the toe against the lateral load at 0.6W or 0.7E
SlidingFriction μ N plus the optional lateral bearing, against the lateral load at 0.6W or 0.7E
Soil bearingEvery ASD combination of ASCE 7-22 2.4, no tension between footing and soil

The stem is checked at the top of the footing, where the moment is largest. The drawing is the wall section with the stem bar, the footing and grade.

Limitations

  • One foot of a straight cantilevered wall. Pier-and-panel fences, pilasters, serpentine walls (TEK 14-16B Figure 2) and walls between returns are not covered.
  • Free ends without a return carry more wind: TEK 14-16B adds 5 psf over a length equal to the height; Figure 29.3-1 case C gives higher coefficients. Enter the higher pressure for that length.
  • The footing's own reinforcement, dowels and laps, the coping and control joints are not designed.
  • Second-order effects in the stem are neglected (short cantilevers); the footing's own seismic inertia is not added.

Verification examples

Verification status: 8 values compared in 3 examples (0 published, 3 hand calculations from the cited equations): 8 within tolerance, 0 recorded deviations. No published example: every value is a hand calculation. That checks the program against this reading of the code, not the reading itself. Code basis: not yet recorded for this module.

No published calculation of a fence to the current codes is on hand: hand calculations of the wind pressure, the footing stability and bearing, and the stem strength. CMHA TEK 14-16B's Tables 2 and 4 are prescriptive selections (2003 / 2006 IBC, ASCE 7-05, f′m 1,500 psi) and are read backward in the behaviour tests: an 8 ft fence of 8 in. CMU with No. 4 bars at 24 in. under the table's 20 psf (32 psf at strength level) uses about 88 percent of its flexural strength here and fails at twice the spacing; the table's 12 by 42 in. footing passes overturning and bearing on 2,000 psf soil.