Cold-formed steel floor vibration

Walking vibration of a floor of cold-formed C-section joists bearing on walls: the joist panel's natural frequency, its effective weight and the predicted acceleration against the engineer's limit, by AISC Design Guide 11, 2nd Ed. (2016), the method the cold-formed steel industry applies to these floors. Every limit, damping ratio and driving force is an input with the Guide's value prefilled; the Guide gives recommendations, not code limits.

The steel floor vibration type covers beam, joist and girder floors with the girder and combined modes; this type is the joist panel of a cold-formed floor, with a sheathed floor option and the Guide's high-frequency method, which light cold-formed floors often need.

Inputs of the floor vibration

  • Joists: an SSMA designation or custom dimensions, the spacing, the span, the floor width across the joists (Bj is at most two thirds of it), a free edge (Cj = 1.0), and continuity (the effective weight × 1.5 of DG11 4.1.2, your call).
  • Floor: concrete on steel deck (depth above the deck, rib height, unit weight, f′c, and whether the slab acts with the joist: DG11 3.2 takes composite action for vibration where the deck is fastened) or sheathing (its stiffness Ds across the joists, your value from the panel's EI and any topping).
  • Day-to-day loads (DG11 3.3, not design loads): the deck or slab, the actual superimposed dead load, and the live load (11 psf for paper offices in the Guide; less for residences).
  • Criteria: damping ratio β (Table 4-2, cumulative), driving force Po (65 lb), the acceleration limit ao/g (0.5 %g offices and residences), how the limit is taken above 9 Hz, and a minimum frequency (DG11: floors below 3 Hz should be avoided).

Auto-design varies the SSMA joist (lightest first) and the joist spacing, for the least joist steel per square foot. The span, floor, loads, damping and limits are kept.

Checks performed

CheckBasis
Transformed moment of inertia (1.35 Ec, slab width S up to 0.4 L)DG11 3.2
Natural frequency fn = 0.18 √(g/Δ)DG11 Eq. 3-3
Effective width and weight, Bj = Cj (Ds/Dj)^¼ Lj ≤ ⅔ floor width, W = w Bj LjDG11 Eqs. 4-2, 4-3
Walking, fn ≤ 9 Hz: ap/g = Po exp(−0.35 fn)/(β W) ≤ ao/gDG11 Eq. 4-1, Table 4-1
Walking, 9 to 15.4 Hz: equivalent sinusoidal peak acceleration ≤ the limitDG11 Eqs. 2-10, 2-11, Table 2-2
Above 15.4 HzDG11 2.2.2: no criterion (a note)
Minimum frequencyDG11 4.1 (your value)

Limitations

  • Joist panel only: joists on bearing walls or stiff supports. A floor on beams or girders needs the combined mode (the steel floor vibration type).
  • Above 9 Hz the limit of DG11 Figure 2-1 is taken as rising in proportion to the frequency above 8 Hz (the ISO baseline shape the figure follows), to confirm against the code text; choose the flat limit to be conservative.
  • The text of Eq. 2-10 in the library copy is garbled; it was rebuilt from Eqs. 1-6 and 2-7 to 2-9 as the Guide derives it, which gives its printed constant 154 (to confirm against the code text).
  • Rhythmic activity, sensitive equipment, and the joists' strength and deflection are not part of this calculation.

Verification examples

Verification status: 7 values compared in 2 examples (0 published, 2 hand calculations from the cited equations): 7 within tolerance, 0 recorded deviations. No published example: every value is a hand calculation. That checks the program against this reading of the code, not the reading itself. Code basis: not yet recorded for this module.

No published worked example of a cold-formed joist floor is in the free library (the CFSEI technical note on floor vibration is not on disk). The values are hand calculations of DG11 Eqs. 3-3, 4-1 to 4-3 and 2-10 with the SSMA Guide (2022) section properties.